Hurricane Turbine Ventilator www.edmonds.com.au www.hurricanevent.com.au
Sitemap | Distributors | Contact Us
Introducing the Hurricane™ Turbine Ventilator | Meets the highest of standards | Special Features
Current Projects | Past Projects
Hurricane™ Turbine Ventilator Showcase | Static Vents | Egg Crate | Industrial Louvres
Resistance To Leakage During Rain | Test Of Two Wind-Driven Roof Ventilators | Fire-Rated Testing Of Hurricane
How to specify the Hurricane™ | How to calculate Number of Ventilators

Calculate & Specify

How to specify the Hurricane™

 

Specification:

The roof ventilators shall be CSR Edmonds Hurricane Turbine Ventilators as indicated in the drawing. They shall be manufactured from aluminium with vertical turbine vanes and incorporate the Tandaco Bearing System.

The bases shall be vari-pitch or ridge mounting and dampers shall/shall not be provided.

The Ventilators shall be supported by a 15 year warranty as provided by CSR Edmonds. Dee Why NSW Australia.

Easy Calculation:

To determine the number of Hurricanes required to efficiently ventilate a building, refer to the ' EASY CALCULATION FORMULA' and select the throat size required from the Hurricane performance table.

  1. Determine Volume of building in cubin metres (i.e. Length X Width X Height) = VOL
  2. Select air changes per hour from table = A/C
  3. Select the most suitable number of vents for the roof spaced uniformly either side of the ridge with recommened spacing of 5m. Wider industrial buildings may require one or more ventilators per bay = N
  4. Determine L/sec. exhaust capacity required for ventilator for selected number of ventilators = E
    and apply equation:
  5. E = VOL X A/C X 0.278
    N

  6. Select wind speed required from Ventilator Capacity Table.
  7. Select the ventilator throat size which will provide the exhaust rate nearest to, but not less that, the calculated figure.
    (Note: 0.278 converts M3/hr to Litres/second.)
EXAMPLE
  1. Building 45 m (L) x 20 m (W) x 5m (H) = 4500 m³ - VOL
  2. Air Changes per hour required, say 5 - A/C
  3. Number of Vents selected, say 8 Hurricane - N
  4. Exhaust Capacity required per Ventilator - E
  5. 4500 x 5 x 0.278 = 781 L/s per vent
    8

  6. Average Sydney wind velocity of 12km/h selected.
  7. From Performance Table select 8 off H450 Hurricane Ventilators

 

    Performance Table (See Comments Below)
    Throat size Of Ventilator (mm) Exhaust Capacity Litres per Second
    Wind 6km/h Wind 12km/h Wind 16km/h
    H100 14 33 42
    H150 110 210 277
    H300 270 480 620
    H400 370 630 800
    H450 480 790 990
    H500 540 900 1240
    H600 620 1104 1420
    H700 944 1630 2090
    H800 1233 2131 2730
    H900 1560 2700 3460

     

    Comments On Exhaust Rates:

    Hurricane vent exhaust rates are nominally based around an original ASHRAE measure for predicting the performance of gravity discharge vents with modification for the turbine action of the ventilators. The calculations assume 6m stack height and 10 °C temperature differential. A similar calculation has been used by most vent manufacturers around the globe. The modified formula makes no allowance for differences in vent exhaust efficiency due to vent design or weight.

    It is not possible under present technologies to measure the flow rate of a vent in situ. Australian Standard 4740:2000, which measures discharge and flow coefficients for rotary vents over a plenum chamber at zero stack height and nil temperature differential, indicates that vent flow rates are probably 30-40% of that provided by the modified formula. Some designs, such as Hurricane, have superior flow coefficients to spherical vane vents while any obstructions in the throat of a ventilator, such as a fan blade or motor, will decrease the discharge coefficient.

    Regardless of the discrepancy between flow rates determining by the modified ASHRAE formula and AS4740:2000, the present generally accepted recommendations for air exchange rates, when applied to flow rates determined by the 'formula', produce acceptable conditions for workplaces.



    hurricane

     

    Table of Recommended Air Changes Per Hour

    Factories and workshops
    5 to 10
    Warehouses
    5 to 8
    Gymnasiums and squash courts
    5 to 10

    Assembly halls

    10 to 15
    Garages
    10 to 15
    Toilets
    12 to 15
    Laundries
    12 to 20
    Air change rate must perform to the local health department's code covering the type of installation.
    Stables
    Air change rate is dependent upon the
    number of animals confined,
    but can range between 10 to 50.
    Piggeries
    Poultry houses

     

    VENTILATOR SIZE APPROXIMATE DIMENSIONS WEIGHT (kg)
    DIM "A" DIM "B" DIM "C"

    H100

    107 313 290 1.8
    H150 155 363 332 2.4
    H300 308 500 477 4.9
    H400 410 564 561 6.3
    H450 462 658 648 8.1
    H500 511 700 702 9.2
    H600 602 724 766 12.8
    H700 705 796 876 15.8
    H800 799 858 1003 20.6
    H900 897 936 1096 24.1

     

Dimensions may alter from time to time.

Average Wind Velocities

During the hot months of November to March the daily recorded wind velocities in Australian capital cities exceed 6 to 10 km/hr for 96% of the hours between noon and 3pm.

NOTE: A wind speed of 6 to 10km/hr is defined as a light breeze. Wind is felt on the face, leaves rustle and vanes move by wind.

The average wind velocities for a 12 month period in km/hr are:
Sydney 12.5, Brisbane 10, Melbourne 13, Adelaide 14.4, Perth 14.4, Darwin 9.8, Hobart 11.5, Canberra 6.4. (Source : Bureau of Meteorology).

CSR Edmonds About CSR Edmonds | Sitemap | Contact Us | © 2007 CSR Edmonds - Site Design by Leon Fernandes

          CSR Building Products - ABN: 55 008 631 356

© 2006 CSR Edmonds - Site Design by Leon Fernandes